circuit breaker basic frame, ComPact NS 2500N, 85/50 kA at 220/415 VAC, 2500 A, fixed, manually operated, without trip unit, 3 P

317,116.00

Schneider’s purpose is to empower all to make the most of our energy and resources, bridging progress and sustainability for all. At Schneider, we call this Life Is On.

We believe access to energy and digital is a basic human right. Our generation is facing a tectonic shift in energy transition and industrial revolution catalyzed by accelerated digitization in a more electric world. Electricity is the most efficient and best vector for decarbonization; combined with circular economy approach, we will achieve climate-positive impact as part of the United Nations Sustainable Development Goals.

Description

PRODUCT DETAILS:

range: ComPact
range of product: ComPact NS1600b…3200
device short name: Compact NS2500N
product or component type: Basic frame
device application: Distribution
Number of poles: 3P
[In] rated current 2500 A at 50 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
network type: AC

network frequency: 50/60 Hz
suitability for isolation Yes conforming to EN/IEC 60947-2
utilization category Category: B

[Icu] rated ultimate short-circuit breaking capacity

85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2

Performance level N 50 kA 415 V AC
control type: Toggle
mounting mode: Fixed

[Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2

[Ics] rated service short-circuit breaking capacity

65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
65 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
65 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
52 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
65 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)

[Icw] rated short-time withstand current

32 kA 3 s conforming to IEC 60947-2
integral instant protection 130 kA
mechanical durability 5000 cycles conforming to IEC 60947-2
electrical durability 1000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
2000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
2000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
3000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2

Height (H): 350 mm
Width (W): 420 mm
Depth (D): 160 mm